二手 TRANE CVHF049FA1X0LCN2767W7E7TCC0000000EA1G0000000003B1 #9014869 待售
網址複製成功!
單擊可縮放
ID: 9014869
優質的: 2002
Chiller, 485 ton
42,955 hrs
Chiller:
Chiller heating or cooling mode cooling
Active chilled water setpoint: 42.0°F
Active chilled water setpoint source: front panel
Active current limit setpoint: 100.0% RLA
Active current limit setpoint source: front panel
Evaporator entering water temperature: 47.8°F
Evaporator leaving water temperature: 41.6°F
Evaporator pump control: on
Evaporator water flow switch status (unfiltered): flow
Chiller control signal target: 46.3%
Condenser entering water temperature: 74.2°F
Condenser leaving water temperature: 82.8°F
Condenser pump control: on
Condenser water flow switch status: flow
Chilled water softload target: 42.0°F
Current limit softload target: 100.0%
Event max: 125
Timer max: 60
Circuit:
Evaporator saturated refrigerant temperature: 40.9°F
Evaporator refrigerant pressure: -8.8 psi gauge
Evaporator approach temperature: 0.7°F
Condenser saturated refrigerant temperature: 83.0°F
Condenser refrigerant pressure: 0.0 psi gauge
Condenser approach temperature: 0.3°F
High pressure cutout circuit on
Head relief request relay: off
Maximum capacity relay: off
Compressor:
Compressor refrigerant discharge temperature: 83.1°F
Oil tank pressure: -9.1 psi gauge
Oil pump discharge pressure: 11.4 psi gauge
Oil differential pressure: 20.3 psid
Oil tank temperature: 110.3°F
Oil pump command: on
Oil heater command: on
Inboard bearing temperature: 108.4°F
Outboard bearing temperature: 95.6°F
Inlet guide vane position first stage: 26.9%
Inlet guide vane position first stage: 13,685 steps
Motor:
Restart Inhibit Time (MP): 0:00 mins:secs
Starter Current L1 %RLA: 56.5 % RLA
Starter Current L2 %RLA: 57.5 % RLA
Starter Current L3 %RLA: 57.3 % RLA
Starter Current L1 Amps: 215.0 amps
Starter Current L2 Amps: 220.0 amps
Starter Current L3 Amps: 219.0 amps
Starter Voltage Phase AB: 480 volts
Starter Voltage Phase BC: 481 volts
Starter Voltage Phase CA: 479 volts
Average Line Current: 57.1 % RLA
Average Line Current: 218.0 amps
Starter Max Current: 55.9 % RLA
Starter Average Phase Voltage: 480 volts
Starter Load Power Factor: 0.81
Starter Power Consumption: 135 kW
Starter Power Demand: 62 kW
Starter Energy Consumption - Resettable: 3,673,414 kWh
Starter Energy Consumption Last Reset December 31, 1979 12:00:00 AM
Starter Energy Consumption - Non Resettable: 3,673,414 kWh
AFD Output Power: 125 kW
AFD DC Bus Voltage: 646 volts
Motor Winding Temperature #1: 92.9 °F
Motor Winding Temperature #2: 92.9 °F
Motor Winding Temperature #3: 92.4 °F
AFD Transistor Temperature: 112.3 °F
Speed: 3,399 rpm
Frequency: 57.0 Hz
Frequency Command: 57.0 Hz
Boundary Pressure Coefficient: 0.57
Pressure Coefficient: 0.58
Re-optimization Time Remaining: 00:00 hrs:mins
AFD Last Diagnostic Code (decimal): 0
Purge:
Time Until Next Purge Run: 0:00 mins:secs
Daily Pumpout-24 Hours: 1:16 mins:secs
Average Daily Pumpout-7 Days: 1:03 mins:secs
Chiller On-7 Days: 6.3 %
Pumpout Chiller On-7 Days: 6.7 %
Pumpout Chiller Off-7 Days: 93.3 %
Refrigeration-Life: 41630:56 hrs:mins
Pumpout-Life: 16788:30 mins:secs
Purge Refrigerant Compressor Suction Temp: 80.6 °F
Purge Carbon Tank Temp: 74.3 °F
Purge Liquid Temperature: 83.0 °F
Pumpout Time Since Last Regeneration: 78:50 mins:secs
Time at Last Regeneration: March 14, 2011 1:52:00 PM
Pumpout Total at Last Regeneration: 16709:40 mins:secs
Absorptive Capacity: 84.2 %
Carbon Regen Cycles: 67
2002 vintage.
TRANE CVHF049FA1X0LCN2767W7E7TCC0000000EA1G0000000003B1冷卻器是一種工業級空調設備,專為商業級應用而設計.它是為任何類型的商業設置量身定制的高效可變空氣量(VAV)系統,包括辦公室、零售商店、餐廳、學校、倉庫和許多其他工業設置。它是利用最新技術實現節能減排的節能空調解決方案。這種冷卻器的主要部件是壓縮機、冷凝器、蒸發器、膨脹閥和風扇馬達。壓縮機是一個單一的螺絲設計,允許一個一致和可靠的輸出制冷劑氣體蒸發器。冷凝器的設計目的是從返回的制冷劑中提取熱量,使其能夠向下冷卻,從而為調節的空間提供必要的冷卻。蒸發器線圈是多行線圈設計,允許更有效地將熱量傳遞到循環空氣中,並允許空氣冷卻到所需溫度。膨脹閥有助於輸送制冷劑氣體和保持機器上的恒定壓力。最後風扇馬達進一步幫助循環冷卻空氣在整個空間。這款TRANE冷卻器還可以設置各種控制器和配件,以實現最大效率和用戶舒適度。SSCP控制器可用於通過對工具進行智能監控、提供診斷信息和數據記錄來實現高效操作。許多附件如變頻驅動器、節能器和其他設備也可以連接到資產,以確保最佳性能。所有這些組件都經過設計和編程,能夠完美和諧地工作,提供更高的舒適度和更低的能源成本。CVHF049FA1X0LCN2767W7E7TCC0000000EA1G0000000003B1冷卻器在商用HVAC環境中具有廣泛的優勢。它們不僅極其可靠高效,還會因為精確的溫度控制而降低能源成本,減少排放,提供更安全的工作環境。VAV模型還允許在每個區域進行獨立的溫度控制,讓每個用戶在自己的空間中享受到完美的溫度。方便的安裝和維護使其成為任何商業場所的理想空調解決方案。
還沒有評論